Application: In fixed installations, in dry, wet places, outdoors or in the ground. Its construction allows use in places where there are risks of mechanical damage. This cable has an increased delay in the propagation of the conf flame. IEC 60332-1 and IEC 60332-3-24 Cat.C
Construction:
1.Conductor - Copper : solid (RE) / Stranded (RM/SM)
2.Insulation - Polyvinylchloride (PVC)
3.Filling - PVC or plastic strips
4.Armor - Cold rolled steel strip
5.Outer mantle - Polyvinylchloride (PVC) Black, UV-resistant
Standards: SP 07/2023
Color Identification Code: According to SR HD 308 S2
Electrical Performance:
Rated voltage UO/U: 600/1000 Volt
Test Voltage: [V]AC 4000
Short circuit time max. [sec] 5
Minimum radius of curvature Min 12 x cable diameter
Temperature range: -30°C till +70°C
Max. short circuit temp. °C 160°C
Fire classification CPR class: Eca